Omron PLC and Siemens touch screen Communication setting method

OMRON PLC can not communicate with TP177B / DP touch screen,
  
But TP177A / DP and other communication with the screen (have repeatedly tested)Specific settings Communication Notes:


(1) All communication settings (HMI and PLC) must be consistent (station number, baud rate, parity, etc.,
   
Use the default values ​​here namely: “9600,7, Even / even, 2”);


(2) CPU-42H 4 feet should be appropriated for “ON” position, that is PRPHL Setup, non-Auto;


(3) Select the network type “SYSMAC WAY”, while the network settings driven by:
   
“COM1,9600; 7, Even, 2” standard;


(4) The key is to work properly PLC communication in “Monitor” mode;


(5) only in programming mode can only be transferred to the PLC is set to go;


(6) OMRON RS422 (CJ1W-CIF11) expansion modules 1-4 feet set “OFF”,
   
5-6 feet is set to “ON”;


(7) If no special requirements, the default setting is usually the best setting;Siemens touch screen connection method OMRON PLC communication line (RS-422A / CJ1W-CIF11)


  
HMI                     PLC
   
8
                     RDA-
   
3
                     RDB +
   
9
                     SDA-
   
4
                     SDB +Where: To meet the standard resistor and a 220 ohm / 2W between “RDA-” and “RDB