OMRON PLC can not communicate with TP177B / DP touch screen,
But TP177A / DP and other communication with the screen (have repeatedly tested)Specific settings Communication Notes:
(1) All communication settings (HMI and PLC) must be consistent (station number, baud rate, parity, etc.,
Use the default values here namely: “9600,7, Even / even, 2”);
(2) CPU-42H 4 feet should be appropriated for “ON” position, that is PRPHL Setup, non-Auto;
(3) Select the network type “SYSMAC WAY”, while the network settings driven by:
“COM1,9600; 7, Even, 2” standard;
(4) The key is to work properly PLC communication in “Monitor” mode;
(5) only in programming mode can only be transferred to the PLC is set to go;
(6) OMRON RS422 (CJ1W-CIF11) expansion modules 1-4 feet set “OFF”,
5-6 feet is set to “ON”;
(7) If no special requirements, the default setting is usually the best setting;Siemens touch screen connection method OMRON PLC communication line (RS-422A / CJ1W-CIF11)
HMI PLC
8 RDA-
3 RDB +
9 SDA-
4 SDB +Where: To meet the standard resistor and a 220 ohm / 2W between “RDA-” and “RDB