Omron DRM21 module prompts E2 error, how to do?

Cause: indicates that the network communication timeout. Countermeasures: 

Check the main station must use the same baud rate from the station;
 
Check the wiring of communication cable is loose;

 
whether the two terminals of the network terminating resistor;

 
check the current speed and distance network, consider reducing the baud rate of the network, using 125Kbps baud rate for communication;

 
recommended DeviceNet dedicated cable network;


Whether there is signal interference around the communication apparatus.