Siemens PLC with four buttons control the four light – Ladder Diagram

                              input        I0.0           SB1               button1 Light control I0.1        SB2 button2                  Light control I0.2         SB3 button3 Light control I0.3         SB4 button4 Light control output Q0.0          EL1 light1 illumination Q0.1          EL2 light2 illumination Q0.2           EL3 light3 illumination Q0.3          EL4 light 4 illumination

Omron DRM21 module prompts E2 error, how to do?

Cause: indicates that the network communication timeout. Countermeasures: ① Check the main station must use the same baud rate from the station; ② Check the wiring of communication cable is loose; ③ whether the two terminals of the network terminating resistor; ④ check the current speed and distance network, consider reducing the baud rate of the network, using 125Kbps … Continue reading Omron DRM21 module prompts E2 error, how to do?

Omron DRM21 module prompts D5 error, how to do?

Reason: registered in the scan list from the station does not exist or is a local master node number is registered in the scan list of the master station. Countermeasures: ① initial commissioning or increase / decrease the slave node: a. Check the baud rate from the master station, you need to set the same;b. Using CX-Integrator software … Continue reading Omron DRM21 module prompts D5 error, how to do?

How do Omron CQM1H and Delta inverter communication

Can, in general, the drive can be controlled in various ways, such as using analog output control inverter, OMRON CQM1H or use the protocol macro function of the inverter communication control, but requires the drive belt 422/485 communications port, If the drive supports DEVICENET protocol, it can also be linked directly into our COMPOBUS / … Continue reading How do Omron CQM1H and Delta inverter communication

Omron PLC Failure Analysis and Troubleshooting

1, Q: What kind of floating-point advantage in the result of the operation, he is not a small point and carry bit? Floating point and double precision floating point, what kind of difference?A: decimal floating point arithmetic with support, which is its advantage, floating-point operations per participation operations accounted for two-channel and double precision floating … Continue reading Omron PLC Failure Analysis and Troubleshooting

Omron PLC and temperature meter 485 serial communication realization

Omron PLC and other instruments or communications equipment (whether OMRON instruments or third-party instrumentation), with the use of serial communication protocol macro module or template, for the corresponding procedures according to the instrument or device communication protocol, establish the appropriate communication channel, it the instrument can read and write.    I worked with third-party customers for over-temperature … Continue reading Omron PLC and temperature meter 485 serial communication realization